FRSI - The Surface Temperature Factor

Surface condensation and mould growth are more likely when buildings have high levels of internal humidity and poor detailing of insulation.


Part L specifies how to reduce mould risk in buildings and refers to BRE’s information paper IP1/06. This paper explains how to calculate the surface temperature factor, or fRsi. The fRsi value is the ratio of the lowest internal surface temperature (Ti) to the total temperature difference across the structure (dT or ΔT) under standard conditions. For Ireland and the UK, 20C is used for the internal temperature and 0C for the external temperature.


The higher the fRsi value, the warmer the internal surface under those conditions, and the lower the mould risk on that surface or point. For dwellings, the fRsi value must be at least 0.75. This means the coldest surface temperature in a dwelling can be 15C, with a temperature difference of 20C. 


At 20C and 60% RH inside, 15C is the surface temperature where RH reaches 80%. This is the threshold for mould to start growing hence the 0.75 ratio.

Contact Us

email - info@thermalbridgecalcs.com

Call: 07441 424 875 (UK) / +44 7441 424 875

Get in touch now, for questions or to schedule a consultation!

Adjuntar archivos
Datos adjuntos (0)

Este sitio está protegido por reCAPTCHA y aplican las Política de privacidad y los Términos de servicio de Google.

Cancelar
Elmhurst’s Psi-Value Competency Scheme
Passive House Certified Designers
  • Passive House Certified Designers
  • Elmhurst’s Psi-Value Competency Scheme
  • Passive House Certified Designers
  • Elmhurst’s Psi-Value Competency Scheme
  • Passive House Certified Designers

Thermalbridgecalcs.com

Copyright © 2026 Thermal Bridge Calcs - All rights reserved